# Cold Chain

The obvious fix undid itself every 90 seconds. The lab found why and had six cases cold in under three minutes.

HI Cyber Con CTF 2026. Hardware. Published 2 November 2026. Challenge by Hidden Investigations.

## The brief

> ColdLink services the refrigeration case controllers at a regional supermarket chain. Overnight, something forced every refrigerated case into continuous defrost. Work out how to authenticate to the controller, find what is forcing the defrost, and bring all six cases back under the compliance ceiling, and keep them there. The controller is stubborn: a naive fix doesn't stick.

- cold-chain.zip, 6.4 KB

## In short

A supermarket's refrigeration controller had every case stuck in defrost. The technician toolkit carried the fleet wide login key, and a maintenance macro put the defrost schedule back every 90 seconds. The lab switched off the macro first, then deleted the schedule, and the cases held under 5 °C.

## Six cases stuck in defrost

All six cases, from DAIRY-1 to BEVERAGE-6, sat at 12.00 °C in defrost against a 2.0 °C setpoint. Compliance meant every case under 5 °C, held for 60 seconds.

## The toolkit carried the fleet key

The technician client hardcodes one master key for the whole fleet. The login answer is the first 16 hex digits of SHA-256 over that key, the serial and a nonce, and the controller sends serial and nonce before login.

## A macro that undoes the fix

Schedule S9, WINTER_DEFROST_ALL, forces defrost on every case. Macro M2, AUTO_WINTERIZE, runs every 90 seconds and turns S9 back on if anyone removes it. The sample historian log shows exactly that loop.

## Macro first, then schedule

Over one connection the lab sent MACRO DISABLE M2, then SCHED DEL S9. With the macro off, nothing could bring the schedule back, and the cases went back to cooling.

## Cold, and held for 67 seconds

The cases dropped under 5 °C and stayed there. At 67 seconds held, STATUS reported compliant=1 with 6 of 6 cases cold and released the flag. A fresh connection later read 2.31 °C in every case.

## The insight

Deleting the defrost schedule treated the symptom. The macro that restored it every 90 seconds was the cause, so it had to go first.

## The flag

hiCTF{cold_chain_restored_defrost_cleared_44c895406a}